Description
Description: Quantity: 1 piece
Coil rated voltage (V): AC200
Applicable motor capacity (200-240V) (kW): Three-phase squirrel-cage motor (AC-3 class): 4
Applicable motor capacity (380-440V) (kW): Three-phase squirrel-cage motor (AC-3 class) 7.5
Applicable motor capacity (500-550V) (kW): Three-phase squirrel-cage motor (AC-3 class) 7.5
Applicable motor capacity (200-220V) (kW): Three-phase squirrel-cage motor (AC-3 class): 4
Part number: MSO-T21 3.7KW 200V AC200V
Motor capacity (kW): 3.7
Auxiliary contacts: 2a2b
Frame: T21
Compatible thermal relay: 2-element thermal relay included, (model name): TH-T25
Heater call (A): 15
Heat element rated adjustment range (A): 12-18
Coil rated voltage (V): AC200
Type: Open type
Category: Electromagnetic Contactor
Operating method: Non-reversible
Main circuit voltage (V): 200
Specifications: Terminal section specifications: Standard specifications, operating coil input: Continuous/7VA, instantaneous on/75VA
Length (mm): 128
Width (mm): 63
Thickness (mm): 82
Weight (kg): 0.58
Mounting method: IEC 35mm rail, screws
Model: AC Operated Type
Frequency (Hz): 50/60
Series: MSO-T
Rated insulation voltage (V): 690
Rated usage current (A): Three-phase squirrel-cage motor (AC-3 class): (200-220V) 18/(380-440V) 18/(500-550V) 17, resistive load (AC-1 class) (200-240V): 32/(380-440V): 32
Mechanical durability: 10 million cycles
Electrical durability: AC-3 class: 2 million cycles, AC-4 class: 30 thousand cycles, AC-1 class: 500 thousand cycles
Rated impulse withstand voltage (kV): 6
Pollution degree (operating environment): 3
Switching frequency (times/hour): AC-3 class: 1800, AC-4 class: 300, AC-1 class: 1200
Open thermal current (A): 32
Operating method: Operating coil, operating circuit: Standard specifications
Applicable motor capacity (200-240V) (kW): Three-phase squirrel-cage motor (AC-3 class): 4
Applicable motor capacity (380-440V) (kW): Three-phase squirrel-cage motor (AC-3 class) 7.5
Applicable motor capacity (500-550V) (kW): Three-phase squirrel-cage motor (AC-3 class) 7.5
Applicable motor capacity (200-220V) (kW): Three-phase squirrel-cage motor (AC-3 class): 4
The miniaturization of the Electromagnetic Contactor has realized miniaturization across many ratings.
By standard equipping a terminal cover, the effort of specifying different model names for customers and arranging options is reduced, leading to inventory reduction and cost reduction effects from the cover. Of course, it also improves safety as protection for the charging part.
In the old series, the number of operating coil ratings was reduced from 14 types to 8 types, while expanding the applicable voltage range. This not only reduces customer inventory but also achieves shorter delivery times through the consolidation of coil manufacturing types.
It is suitable for motor overload and restraint protection.