Description
Quantity: 1 piece
Operation Method: Non-reversible
Case Presence: Without Case Cover
Coil Rated Voltage (V): AC100
Part Number: SC-N1 Coil AC100V 2a2b
Type: Electromagnetic Contactor
Applicable Motor Capacity (100-120V) (kW): Single-phase Motor (AC-3): 1.2
Rated Current (A): 50
Rated Operating Voltage (V): 220/440
Auxiliary Contacts: 2a2b
Length (mm): 96
Width (mm): 87
Thickness (mm): 74
Frame: N1 Type
Coil Rated Voltage (V): AC100
Release Voltage (V): 50Hz: 75-105, 60Hz: 85-115
Standards: International Standards (IEC, EN, VDE, BS, UL, CSA certified)
Model: SC-N1
Mass (kg): 0.59
Breaking Current (A) for Three-phase Squirrel-cage Motor (AC-3): 220V: 320, 440V: 320
Mounting Screw: 2-M4
Loss (W): 200V 50Hz: 3.6, 220V 60Hz: 3.8
Compatible Thermal Relay: TR-N2
Compatible Rail Width (mm): 35
Electrical Durability: 2 million times (AC-3), 30,000 times (AC-4), 500,000 times (AC-1)
Mechanical Durability: 10 million times
Electromagnet Capacity (VA) / During Operation 200V 50Hz: 120, 220V 60Hz: 135
Electromagnet Capacity (VA) / During Storage 200V 50Hz: 12.7, 220V 60Hz: 12.4
Operating Time (ms): Coil ON 闂?Main Contact ON: 10-17, Coil OFF 闂?Main Contact OFF: 6-17
Closed Loop Voltage (V): 50Hz: 110-130, 60Hz: 120-140
Rated Capacity (kW) for Three-phase Squirrel-cage Motor (AC-3): (200-240V) 5.5, (380-440V) 11
Rated Operating Current (A) for Three-phase Squirrel-cage Motor (AC-3): (200-240V) 26, (380-440V) 25
Accessories: Includes 2 heat element thermal relay
Specifications: –
Protection Structure: Without Case Cover
Contact Configuration: [Auxiliary] Double Contact
Operation Method: Non-reversible
Reset Method: Manual
Excitation Method: –
Coil Voltage (V): AC100
Opening and Closing Frequency (times/hour): 1200 (AC-3), 300 (AC-4)